ARD CORE Single Phase
Previous
Next
TECHNOLOGY: | True On-Line, Double Conversion |
CLASSIFICATION CODE: | VFI – SS – 111 (zg. z PN-EN 62040-3) |
POWER RANGE: | 1, 2, 3, 6, 10 kVA |
PHASE CONFIGURATION: | 1:1 (Plug&Play) |
SOFTWARE: | ViewPower |
APPLICATIONS:
Servers, Workstations, lighting, lab equipment, security systems, automation and control systems
- True On-Line Double Conversion Technology (EN 62040-3) provides perfect output voltage parameters, regardless of the input voltage and the load.
- Automatic Bypass (Static Switch) provides continuous load supply in critical conditions, such as overheating or inverter failure.
- Frequency converter feature lets you set the output frequency to 50Hz or 60Hz.
- USB, RS-232, Dry Contact for UPS (Uninterruptible Power Supply) and load supervision and control.
- TVSS surge suppressors and built-in RJ-45 connectors guarantee safety of data send through network.
- Ethernet Interface for computer-network communication with SNMP protocol support
- Software controlled output receptacles enable managing groups of load.
- Small dimensions – all power units have 2U only (1-10kVA), it makes installation and operation easy and compact.
- High efficiency reduces heat dissipation and decreases operating costs.
- ECO-Mode gives possibility of significant cost reduction and in practice stops heat emission. Efficiency up to 99%.
- Backup time extension possibility provides exact fitting for required autonomy time.
- Automatic diagnostics ensure that components and parameters are controlled without user interference.
- High input power factor reduces the value of current drawn from the mains.
- High output power factor (PF=1 for 6-10kVA) allows load of versatile characteristics to be connected.
- Wide input voltage range for normal mode ensures that the batteries are used only if necessary – in fact, only when the input voltage is completely lost.
- Wide input frequency range for normal mode gives possibility for seamless operation with different power sources – as mains or the generating set.
- Automatic start up ensures maintenance-free operation even after the unit was switched-off after long time mains failure.
- Advanced Battery Management gives reliability of optimal charging and using batteries, elongates its lifetime and reduces operation costs.
- Battery start up feature enables unit start up without mains supply.
- Excellent voltage quality is provided by IGBT inverter and high-frequency PWM modulation method; the output voltage has always stable parameters, independent of input disturbances and load characteristics.
- High overload capacity indicates power reliability during transient conditions and high resistance on handling faults.
- Advanced power management software provides full control of UPS.
- User configurable settings – nominal voltages, frequencies, preferred operating modes, ways of communication – widens the range of possible applications.
- REPO – enables remote emergency power off, in case of emergency
- Extra charger inbuilds in 6 and 10kVA models
- Possibility to parallel units 6 and 10kVA for capacity or redundancy.
Model | CORE 1K | CORE 2K | CORE 3K | CORE 6K | CORE 10K |
Rating | 900W 1000VA | 1800W 2000VA | 2700W 3000VA | 6000W 6000VA | 10000W 10000VA |
Phases In:Out | 1:1 |
Input |
Mains voltage | 208 / 220 / 230 / 240 Vac |
Voltage range | 30% ÷ +30% @ 100% ≥ Load > 80% -40% ÷ +30% @ 80% ≥ Load > 70% -48% ÷ +30% @ 70% ≥ Load > 60% -52% ÷ +30% @ 70% ≥ Load > 0% |
Frequency | 50 / 60 Hz |
Frequency range | -20% ÷ +20% |
THDi | <3% |
Power factor | ≥0,99 |
Output |
Nominal voltage | 208 / 220 / 230 / 240 Vac | ||||
Power factor | 0,9 | 1,0 | |||
Voltage regulation static/dynamic | ±1% / ±3% | ||||
Nominal frequency | 50 / 60 ± 0,05 Hz | ||||
Overload | 110% – no limit, 130% – 5 min, 140% – 30 sec., >140% – 1,5 sec | 110%-10min, 130% – 1 min., > 130% – 1 sec. | |||
Efficiency Normal Mode | >92% | >95% | |||
Efficiency Eco Mode | 99% | ||||
Programmable output receptacles | 1 x 4pcs | 1 x 4pcs | 1 x 4pcs | n/a | |
Output receptacles | IEC320-C13 x8 | IEC320-C13 x8 | IEC320-C13 x8 IEC320-C19 x1 | n/a (possibility to add external PDU) | |
Connection termianl | n/a (Plug&Play) | yes | |||
Crest factor | 3:1 |
Batteries |
Backup time Internal batteries / + 1 x EBM | 100% load | 8 / 32 | 4 / 20 | 4 / 20 | – / 9 | – / 3 |
75% load | 12 / 43 | 7 / 30 | 7 / 28 | – / 13 | – / 6 | |
50% load | 20 / 73 | 12 / 45 | 12 / 42 | – / 21 | – / 11 | |
Internal batteries | 3 x 7/9Ah | 4 x 7/9Ah | 6 x 7/ 9Ah | – | – | |
Cold start | avaiable | |||||
External battery socket | avaiable | |||||
Charging time | 4 hours to 90% of capacity | |||||
Charging method | According to DIN 41773 with 3 –stage charging for extend battery life |
Weight and dimensions |
UPS weight and dimensions (WxDxH) | 438 x 410 x 88 (2U) | 438 x 510 x 88 (2U) | 438 x 630 x 88 (2U) | 438 x 665 x 88 (2U) | 438 x 665 x 88 (2U) |
14,2 kg | 19,5 kg | 27,4 kg | 17,0 kg | 20,0 kg | |
EBM weight and dimensions (WxDxH) | 438 x 410 x 88 | 438 x 510 x 88 (2U) | 438 x 630 x 88 (2U) | 438 x 630 x 133 (3U) | 438 x 630 x 133 (3U) |
21,3 kg | 28,5 kg | 40,8 kg | 63,0 kg | 63,0 kg |
Communications |
User interface | LCD panel + sound alarm |
Communications | Standard: RS232, USB, TVSS, SNMP Slot, REPO Options: AS-400 card, SNMP card |
Environmental |
Audible noise | <45 dB | <50 dB | |
Operating temperature | 0°C ÷ 45°C | ||
Reccomended temperature | 15°C ÷ 25°C | ||
Storage temperature | -25°C ÷ 55°C | ||
Humidity | 0 ÷ 95% (non-condensing) |
Standards |
EMC markings | EN 62040-2:2005, EN 62040-2:2006 | ||
Safety markings | IEC62040-1-1, CE, 62040-3 :2001 |
Options |
– SNMP card – Environmental sensor (EMD) – External maintenace bypass – REPO switch | – External battery modules – 19’’ Rail Kit – AS-400 card |